TM 55-4920-328-13
Engine Low Oil Pressure (11)
Engine Chip Detector (12)
Services Inoperative (13)
NI Overspeed (14)
Engine Low Fuel Pressure (14A)
High EGT (15)
Nil Overspeed (16)
Engine Low Oil Level (17)
Water Brake System (18)
Aborted Start (19)
Water Brake Low Oil Pressure (20)
Water Brake BRG H20 (21)
Water Brake Low Oil Flow (22)
Cooling Tower Low H20 Level (23)
The front panel mounts four INSTRUMENT/CONSOLE
switchlight units with the following lens engraving:
115 VAC 400 Hz (28)
Inst DC (29)
Console DC (30)
26 VAC 400 Hz (31)
The panel also mounts ENGINE, ALARM, and test
switchlight units placarded as follows:
Lamp Test (24)
ACK (25)
Test (26)
Engine DC (27)
The rear panel of the services panel assembly mounts
connectors J1, J2, and J3 for connection of this unit with
other electrical components contained in the system.
The time (Ml) indicator (10, figure 1-25) is a
hermetically-sealed,
digital
readout,
elapsed
time
indicator which displays total accumulated operational
time for the system. The input power required for
operation of the time indicator is provided by 117v ac,
60 Hz power from the diesel engine generator set. Two
solder terminals are provided on the rear face of the
time indicator housing for connection of input power.
There is no reset function incorporated in the design of
the time indicator.
3. Transducer input monitor alarm assembly
4A2. The transducer input monitor alarm assembly (32,
figure 1-25) is located in the lower part of the cabinet
assembly immediately below the writing surface. The
rack-mounted monitor alarm assembly is 19 inches
wide, 3.5 inches high, and 16.5 inches deep. The unit is
a modular, solid state annunciator subsystem which
senses, indicates, and acknowledges alarm inputs from
a series of external sensors. The unit provides output
signals for audible and visual warning of out-of-
tolerance operating conditions during a test. Seven
connectors are installed on the rear panel of the unit for
connection with other electrical components of the
system. The monitor alarm assembly consists of four
sections: sequencing, flasher-audible, set point, and
regulation. Section 1 consists of 11 dual-sequencing,
plug-in circuit boards. Each circuit board operates two
visual alarm lamps. This unit monitors 22 separate
contact closures and generates output signals to Section
2. The flasher-audible part of the unit comprises
Section 2. The section sensed input signals from
Section 1 to cause the audible alarm assembly to sound
and the appropriate annunciator light in the services
panel assembly (9) to flash on and off continuously until
the test technician takes action to acknowledge the
visual warning. Section 3 of the unit contains the set
point circuitry consisting of six plug-in circuit boards,
each utilizing one contact. The regulator section of the
unit (Section 4) contains two circuit boards which are
conditioned by ac input signals to provide regulated
+12v dc and -12v dc voltages to Section 3. When an
out-of-tolerance condition is sensed, the monitor alarm
assembly provides a signal to an audible alarm unit
which
sounds
to
alert
the
test
technician.
Simultaneously, intermittent signals are sent to the
appropriate ALARM DISPLAY annunciator light to cause
the light to flash on and off. The light will continue
flashing until the abnormal condition is cleared, until the
ACK switchlight unit (25, figure 1-25) is depressed, or
until the system is deenergized. When the ACK
switchlight unit is depressed, the annunciator light will
come on and remain continuously on and the audible
alarm will be simultaneously silenced. The unit may be
tested by use of the ALARM TEST switchlight unit.
4. 26 VAC, 400 Hz power supply 4A9. The
26v ac, 400
Hz power supply (41, figure 1-25) is
located in the lower part of the cabinet assembly which
houses the services sub-module (Unit 4), below the
transducer input monitor alarm assembly (32). The
power supply converts 117v ac, 60 Hz to 26v ac, 400 Hz
power. The 26v ac output is variable from 24 to 30
volts; the 115v ac output is variable from 105 to 130
volts. Frequency of the output is variable from 380 to
420 Hz. Two meters are installed on the left side of the
rack-mounted unit to display output voltages and output
current. A dual knob is centrally located to the right of
the meters. This control allows precise adjustment of
the output of the unit. Output jacks are located on the
front panel to provide a source of auxiliary power when
required. A 2-ampere fuse is mounted on the front
panel for line protection. Two other MDL-8 fuses are
mounted on the rear of the
1-50
