TM 10-4930-351-14
0006 00
Table 1. Operator's Preventive Maintenance Checks and Services for AAFARS (Continued)
Item Interval
Location
Procedure
Not Fully Mission
No.
Capable If:
Item to Check/
Service
46
During Liquid Fuel
Perform fuel contamination tests with the Fuel Contamination Test
Fuel tests fail.
Filter-Separator Kit.
47
During Auxiliary Pump Inspect for signs of leakage.
Any Class I, Class
II or Class III fuel
leak is found.
48
During CCR-Nozzle
Inspect handle action to see that it operates smoothly.
Handle fails to
operate smoothly.
49
During Pressure Control Check pressure control for proper operation. Pressure control
Fails to shut off
should shut off as wrinkles are removed from drum.
properly.
50
After
CCR-Nozzle
Inspect for missing or damaged lugs (1). There should be three
Lugs missing or
stayback lugs and nine locking lugs.
damaged.
51
After
CCR-Nozzle
Inspect nozzle housing (2) for leaks.
Any Class I, Class
II or Class III fuel
leak is found.
52
After
CCR-Nozzle
Inspect bonding cable assembly (3) for loose connection, frayed or
Damaged or frayed
damaged cables, bent or damaged plug or clip.
cables. Bent or
damaged plug or
clip.
53
After
CCR-Nozzle
Inspect cap assembly cap (4) for cracks, burrs or damage. Inspect
Damaged cap or
cable for breaks, frays and security.
cable.
54
After
CCR-Nozzle
Inspect coupling assembly (5) for leaks.
Any Class I, Class
II or Class III fuel
leak is found.
2
1
4
5
3
0006 00-11